6. Procedure determining Exclusion Distances

 

6.1 Intentional transmitters

 

This may include radios, communication transmitters, RF ID scanners, WiFi and Bluetooth.

 

(i) Select the equipment.
(ii) Obtain information about the equipment i.e. supplier, manufacturer, model, type specification.
(iii) Confirm ICASA certification.
(iv) Obtain the Effective Radiated Power (ERP) from ICASA certificate.
(v) Using the ERP and with the aid of the graph in Figure 3 above read off the exclusion distance in m for the equipment.
(vi) Repeat the above procedure for all the other intentional transmitting equipment.

 

6.2 Non-intentional transmitters

 

This may include equipment installed or used in the explosives production facilities and may include all the hard-wired equipment i.e. scales, programmable logic control systems, distributed control system, process variable transmitters, various sensors, proximately switches, laser devices, cameras.

 

(i) Select the equipment.
(ii) Confirm whether the equipment has aR5048 CE Mark ivmark, if so, continue with step (iii), if not, then proceed to step (vi).
(iii) Obtain a test report of the equipment from the supplier i.e. model, type, specification.
(iv) Calculate the ERP from the test report and with the aid of the graph of Figure 3 read of the exclusion distance in metres for the equipment.
(v) Repeat the above procedure for all the other non -intentional transmitting equipment.
(vi) Arrange for testing of equipment for RF emissions & immunity to be carried out by an EMC testing laboratory according to Government Gazette 39182 of September 2015.
(vii) Receive from the test laboratory a report showing the Immunity (V/m) and the Effective Radiated Power (dBm or mW).
(viii) Using the ERP and with the aid of the graph in Figure 3 above read off the exclusion distance in m for the equipment.
(ix) Repeat the above procedure for all the other non -intentional transmitting equipment.